CPSC, Thomas & Betts Announce Recall of Emergency Exit Signs

CPSC published this recall on 2003-02-05 under Lights & Signs (Emergency & Exit). Check the official notice for affected models and remedy instructions.

Open the official CPSC recall notice ↗

Official reported fields · missing fields omitted
RecallNumber03520
DescriptionThe recalled exit signs were sold under the Lightalarms, Emergi-Lite, and Dynaray brand names and can be installed in either 120-volt or 277-volt applications. Only signs with a red LED and installed in 277-volt applications need to be repaired. These emergency exit signs could be installed in public buildings such as schools, offices and shopping centers to mark an exit in the event of a power failure and loss of lighting. They have a white or black plastic housing and are 13 ½ inches long, 8-3/8 inches high and 2-7/8 inches deep. Recalled units have a raised bead around the edge of the front face and a rectangular rocker switch on the bottom. The product make, model, and date code is located on a label inside the enclosure. The recalled emergency exit signs were manufactured between January 1997 and June 1999.
LastPublishDate2025-07-08T00:00:00
ProductsName: Emergency Exit Signs · Type: Lights & Signs (Emergency & Exit) · CategoryID: 2030 · NumberOfUnits: About 31,000
HazardsName: The emergency exit signs have an internal electrical component that could overheat and fail, when connected to 277-volt electrical systems, and melt the enclosure, posing a fire hazard.
InjuriesName: There have been 19 reports of these emergency exit signs overheating and smoking or causing melted or damaged enclosures. No injuries have been reported.