Oomi Home / independent public-data directory
Fire Control Panels Recalled by Bosch Security Systems Corp. Due to Alarm Failure Posing a Fire Hazard
CPSC published this recall on 2012-02-15 under Fire or Smoke Alarms. Check the official notice for affected models and remedy instructions.
Open the official CPSC recall notice ↗
| RecallNumber | 12721 |
|---|---|
| Description | The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep. The status, date and time can be seen through a glass screen on the panel door. The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen. The alarm panels featured software versions 1.10, 1.11 and 1.12, which can be determined by installers. They were designed to be used in small to medium-sized facilities in both public and residential buildings. |
| LastPublishDate | 2016-04-14T00:00:00 |
| Products | Name: Fire Alarm Control Panel · Type: Fire or Smoke Alarms · CategoryID: 67943 · NumberOfUnits: About 330 |
| Hazards | Name: On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken. |
| RemedyOptions | Option: New Instructions |
| Injuries | Name: None reported. |
Snapshot retrieved 2026-11-15 UTC. Always verify changes at the official source.