Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO

CPSC published this recall on 2016-03-31 under Fire or Smoke Alarms. Check the official notice for affected models and remedy instructions.

Open the official CPSC recall notice ↗

Official reported fields · missing fields omitted
RecallNumber16134
DescriptionThis recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.
LastPublishDate2016-03-31T00:00:00
ProductsName: Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3) · Type: Fire or Smoke Alarms · CategoryID: 67943 · NumberOfUnits: About 1,000
HazardsName: When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
RemedyOptionsOption: Repair
InjuriesName: No incidents or injuries have been reported.