Oomi Home / independent public-data directory
Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO
CPSC published this recall on 2016-03-31 under Fire or Smoke Alarms. Check the official notice for affected models and remedy instructions.
Open the official CPSC recall notice ↗
| RecallNumber | 16134 |
|---|---|
| Description | This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected. |
| LastPublishDate | 2016-03-31T00:00:00 |
| Products | Name: Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3) · Type: Fire or Smoke Alarms · CategoryID: 67943 · NumberOfUnits: About 1,000 |
| Hazards | Name: When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm. |
| RemedyOptions | Option: Repair |
| Injuries | Name: No incidents or injuries have been reported. |
Snapshot retrieved 2026-11-15 UTC. Always verify changes at the official source.