GE Infrastructure Sensing Recalls Commercial CO2 and Temperature Sensors Due to Fire Hazard

CPSC published this recall on 2010-02-18 under Thermostats/Thermometers/Sensors. Check the official notice for affected models and remedy instructions.

Open the official CPSC recall notice ↗

Official reported fields · missing fields omitted
RecallNumber10141
DescriptionThis recall involves GE Telaire Airestat CO2 and temperature sensors with model numbers T8010, T8010-C, T8011, T8011-C, T5010, T5010-C, T5011 and T5011-C and Carrier Single Beam CO2 and temperature sensors with model numbers 33ZCT55CO2 and 33ZCT56CO2. The sensors are sold for commercial use and are wall-mounted. The sensors have a Telaire, Carrier, or no logo in front of the unit. The model number is not found on the sensor. Determining if a sensor is included in this recall requires inspection of the internal components of the unit.
LastPublishDate2014-05-23T00:00:00
ProductsName: GE Telaire Airestat and Carrier Single Beam Carbon Dioxide (CO2) and Temperature Sensors · Type: Thermostats/Thermometers/Sensors · CategoryID: 2171 · NumberOfUnits: About 9,400 units
HazardsName: The CO2 and temperature sensors can overheat, posing a fire hazard.
InjuriesName: GE has received three reports in which a cracked capacitor caused the product to overheat and smoke. No injuries have been reported.