Schneider Electric Recalls Square D-Brand F and K Frame Circuit Breakers Due to Fire Hazard

CPSC published this recall on 2014-03-18 under Electric Wire or Wiring Systems. Check the official notice for affected models and remedy instructions.

Open the official CPSC recall notice ↗

Official reported fields · missing fields omitted
RecallNumber14134
DescriptionThis recall involves Square D brand models FA, FH, FI and FY one-, two- and three-pole circuit breakers rated 15 to 100 amps, and model KI two- and three-pole circuit breakers rated 110 to 250 amps. The F model breakers were manufactured May 8, 2013 through June 10, 2013 and have date codes 13193 through 13241. The K models were manufactured May 2, 2013 through June 21, 2013 and have date codes 13184 through 13255. The date codes are YYWWD format (example: 13184 = year 2013, week 18, day of the work week 4/ Thursday). The circuit breakers have a yellow label with the words "Square D" or the Square D logo. Model information can be found on the faceplate.
LastPublishDate2015-01-08T00:00:00
ProductsName: Square D branded, molded case F and K frame circuit breakers · Type: Electric Wire or Wiring Systems · CategoryID: 67879 · NumberOfUnits: About 28,400
HazardsName: The circuit breaker can fail to trip when an overload occurs, posing the risk of fire, burn and electric shock.
RemedyOptionsOption: Replace
InjuriesName: None reported.