System Sensor Recalls Reflected Beam Smoke Detectors Due To Failure to Alert Consumers in a Fire (Recall Alert)

CPSC published this recall on 2014-01-28 under Fire or Smoke Alarms. Check the official notice for affected models and remedy instructions.

Open the official CPSC recall notice ↗

Official reported fields · missing fields omitted
RecallNumber14713
DescriptionThis recall involves System Sensor's reflected beam smoke detectors with model number BEAM1224S and date codes 2111 through 3053. The YMMW format date codes stand for (2111) 2012-November-1st week of Nov. through (3053) 2013-May-3rd week of May. The detectors are ivory and black and measure 10 inches high by 7½ inches wide. The model number and date code are printed on a label on the back of the detector's cover and on the product's packaging. The reflected beam smoke detectors were used primarily in commercial buildings as part of the fire alarm system. Detectors used with acceptable power supplies, as listed on the company website, do not need to be replaced.
LastPublishDate2015-05-11T00:00:00
ProductsName: System Sensor reflected beam smoke detectors · Type: Fire or Smoke Alarms · CategoryID: 67943 · NumberOfUnits: About 610
HazardsName: When used with certain power supplies, the reflected beam smoke detectors can fail to send a signal to the fire alarm control panel that sounds the alarm and fail to alert occupants of a fire.
RemedyOptionsOption: Replace
InjuriesName: None reported